On Sat, 11 Sep 2010 11:28:10 +0000, K1TTT wrote:
>They should be at the shack entrance panel. it sounds like you have a common
>misconception about the 'Single Point Ground' concept. THE SPG is the point
>where the cables all come together and enter the shack.
And it appears that you might have some misconception as well. That single
point must also have a low impedance bond (SHORT, BEEFY) to ALL other grounds
in the building -- all ground rods, the mains power service entrance, CATV,
Telco, cold water, structural metal, TV antenna, etc.
73, Jim Brown K9YC