| To: | towertalk@contesting.com |
|---|---|
| Subject: | Re: [TowerTalk] Power line filter question |
| From: | Jim Brown <jim@audiosystemsgroup.com> |
| Reply-to: | jim@audiosystemsgroup.com |
| Date: | Tue, 20 May 2014 22:46:18 -0700 |
| List-post: | <towertalk@contesting.com">mailto:towertalk@contesting.com> |
On 5/20/2014 10:02 PM, Grant Saviers wrote: So why are x uH's of green wire inductance ok in the three wire case and not for a single green wire (engineering pls, not UL regs)? First, if all three conductors go through the choke, a fault on the circuit will blow a breaker faster. Second, at RF, the capacitance between conductors tends to put the conductors in parallel. 73, Jim K9YC _______________________________________________ _______________________________________________ TowerTalk mailing list TowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk |
| <Prev in Thread] | Current Thread | [Next in Thread> |
|---|---|---|
| ||
| Previous by Date: | Re: [TowerTalk] Power line filter question, Grant Saviers |
|---|---|
| Next by Date: | [TowerTalk] Mast/tower design close in guyed by shrouds and spreaders?, Chuck Smallhouse |
| Previous by Thread: | Re: [TowerTalk] Power line filter question, Grant Saviers |
| Next by Thread: | Re: [TowerTalk] Power line filter question, Jim Lux |
| Indexes: | [Date] [Thread] [Top] [All Lists] |