     To do otherwise would split overload return current between the neutral 
and ground wires and delay thermal tripping of the protective circuit breaker 
or fuse at the source.  (A 30A breaker sees only 25A of a 50A overload, for 
example, and lets the load (heater?) just sit there and cook until it flames.)  

73 de
Gene Smar  AD3F



 There must be no path between system neutral and 
> ground anywhere else.