Just in case my experience may help someone...The last 1/2, especially the last 1/4 of a ground rod is often much harder to drive than the first part. I have used a sledge before but... you can bend the rod and then it just seems to want to bend more and not go deeper. Use a length of metal tubing or pipe slid over the end of the rod. You can tape it in place or... This keeps the rod from bending when using a large hammer (sledge.) I use two lengths of pipe. First one is about 2 1/2 ft long. When that starts going into the ground I switch to a shorter one about a foot or so long. I have sledges ranging from 8 lb to 14 lb and can swing them pretty forcefully when needed (6'2" 215 lbs). The pipe over the rod thing works well for me. I also have an electric demo hammer (small electric jack hammer.) I made a rod driving tool for it. I used a piece of conduit driven over a length of a regular chisel made to fit the hammer. Bought it cheap at Harbor Freight and cut it in half. One end is used to make the rod driver tool. I welded the conduit to the cut off chisel. Being thrifty I ground the scrap piece with the chisel tip to the shape of the part that mates with the hammer. My hammer doesn't drive rods in really hard dirt very fast but takes little effort on my part and with patience will do a terrific job. I have never needed the pipe over the rod when driving with the electric hammer but there could be a first time. Good luck. Patrick NJ5G On 1/19/2015 9:19 AM, Jim Lux wrote: On 1/18/15 9:53 PM, Kelly Taylor wrote:It seems to me a valid question to ask on this thread: Do you gain anythingby, for example, drilling a hole to get a ground rod deeper? If you think about it, the answer might not be so simple.The point of a ground rod is to maximize electrical contact with the ground. If you have to drill 48 inches of an eight-foot rod and don't employ some kind of conductive filler (concrete, bentonite, etc.) to bond the rod to the rock, how much better off are you than just putting in a 48-inch rod? Evenif you do use bentonite, is rock a good connection?If that's the case, what would be wrong with cutting the eight-foot rod intotwo 48-inch rods and driving them 96 inches apart?The point of eight- or ten-foot ground rods is to get eight or ten feet ofcontact area, not necessarily to get eight or ten feet deep, yes?Yes, and two short rods would work as well, if not better, than 1 big rod.However, there is a potential depth related issue: soil moisture varies a lot in the first few feet, and in a lot of places, the chemical composition of the soil changes (top soil vs subsoil). That's not really addressed in the building code, though.For what it's worth, the reason the code expresses a preference for Ufer grounds(concrete encased grounding electrodes) is just this sort of problem. A big block of concrete 20 feet long and a foot square is going to have a lot of contact area with the surrounding soil, in a lot of places, so local anomalies of dry or loosely compacted soil aren't going to be as big a problem.Just curious on all this. 73, kelly ve4xt On 1/18/15 10:04 PM, "Bill Aycock" <billaycock@mediacombb.net> wrote:-----Original Message----- From: Bill Aycock Sent: Sunday, January 18, 20157:23 PMTo: Ken Subject: Re: [TowerTalk] w7ekb & ground rods Ken-- I was oncetold (Unofficially) by a power line guy that the length was moreimportantthan depth, and a rod driven at an angle was often the only optionwhen rockwas a problem.However, Mr. Murphy ruled against me and I only knew I had arock problemwhen I had only about 8" left to go. Bill--W4BSG -----OriginalMessage-----From: Ken Sent: Sunday, January 18, 2015 7:00 PM To:maflynn@theflynn.orgCc: towertalk@contesting.com Subject: Re: [TowerTalk]w7ekb & ground rodsIf I may ask, what¹s the ³appropriate tool² when you havea rock layer 40²down? i tried a hammer drill, waste of time. I rented anSDS-MAX hammerand I got one in all the way, four others only made it most ofthe way. Sowhat is the recommendation? Ken WA8JXMOn Jan 18, 2015, at 7:46 PM, Martin A Flynn <maflynn@theflynn.org> wrote: Ran this past one of the code enforcement guys in the county. Surprising response: "We make you buy a UL listed panel board and breakers - what makes you think you can build a grounding system that is equal to UL *and* be able to prove it in court if there is a problem? Buy the listed rod(s) and drive them with the appropriate tool"_______________________________________________ _______________________________________________TowerTalk mailinglistTowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk--- This email has been checked for viruses by Avast antivirussoftware.http://www.avast.com ______________________________________________________________________________________________ TowerTalk mailinglistTowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk_______________________________________________ _______________________________________________ TowerTalk mailing list TowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk_______________________________________________ _______________________________________________ TowerTalk mailing list TowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk _______________________________________________ _______________________________________________ TowerTalk mailing list TowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk |
<Prev in Thread] | Current Thread | [Next in Thread> |
---|---|---|
|
Previous by Date: | Re: [TowerTalk] Fw: w7ekb & ground rods, Brian Carling |
---|---|
Next by Date: | Re: [TowerTalk] Fw: w7ekb & ground rods, Patrick Greenlee |
Previous by Thread: | Re: [TowerTalk] Fw: w7ekb & ground rods, Jim Lux |
Next by Thread: | Re: [TowerTalk] Fw: w7ekb & ground rods, Roger (K8RI) on TT |
Indexes: | [Date] [Thread] [Top] [All Lists] |