In a message dated 5/25/2011 8:29:13 A.M. Pacific Daylight Time,
towertalk-request@contesting.com writes:
> Ok , I have most of my ground system planned out , my plan is to use
copper pipe
(type "L") and silver solder flashing to them from the tower etc...
It all sounds okay except the soldering - don't do it. Any transient
will melt the solder and then you don't have a ground system. Exothermic
(e.g. Cadweld) or compression (e.g. nuts & bolts) are the only acceptable
joining methods for ground systems.
Cheers,
Steve K7LXC