Think about it for a moment... the ground path for the outlet in a residence
is likely #14 wire to the breaker panel. If there were a lightning (or other
transient) event somewhere else in your house, that single wire will carry a
portion of the current to ground. You would be counting on it to carry
almost as much - maybe more - than the protection ground from the panel to
the primary panel ground.
Not a good thing. I've seen it done and it gives me the willies. I can
almost smell smoke...
AWG 4 is, what, $75 for 100 feet? Bonding is cheap protection.
73,
Mickey N4MB