To: | towertalk@contesting.com |
---|---|
Subject: | [TowerTalk] Subject: Re: Cadwelding vs Silver Solder for GroundRadial, Systems |
From: | Phil Camera <kb9cry@comcast.net> |
Date: | Sun, 09 Jul 2006 13:31:57 -0500 |
List-post: | <mailto:towertalk@contesting.com> |
DO NOT Solder (or braze or anything like that) any ground connections. NEC only allows mechanical or exothermic connections. (I wonder why?) As pointed out, CadWelds are NOT expensive and you get the proper connection as well as maintenance free. Do it the right way. #4 bare solid would be minimum size wire for ground radials. Polyphaser recommends one 75 foot long radial for each tower leg (with ground rods spaced along that length as required). -- Phil Camera, KB9CRY Lockport, Illinois _______________________________________________ _______________________________________________ TowerTalk mailing list TowerTalk@contesting.com http://lists.contesting.com/mailman/listinfo/towertalk |
<Prev in Thread] | Current Thread | [Next in Thread> |
---|---|---|
|
Previous by Date: | [TowerTalk] Generator Multi Fuel Conversions/Consumption, Pat Barthelow |
---|---|
Next by Date: | [TowerTalk] Continuous, bonded grounds, JC Smith |
Previous by Thread: | [TowerTalk] Generator Multi Fuel Conversions/Consumption, Pat Barthelow |
Next by Thread: | Re: [TowerTalk] Subject: Re: Cadwelding vs Silver Solder for GroundRadial, Systems, Roger D Johnson |