In a message dated 98-04-25 10:15:27 EDT, ecollins@chickasaw.com writes:
> I have a Rohn 25G 140 foot Tower almost ready to put up.
> The only thing that I need is the cement for the base and the guy anchor
> posts.
> and turnbuckles
>
> I am going to use 3 or 4 inch OD heavy pipe for the southeast and
> southwest guy anchors tall enough to pass over the drive way .
Unless these are VERY strong carbon steel tubes, I would strongly
recommend using I-beam (eye-beam) as it is much stronger than a round pipe
(tube). Are you going to get them engineered? Are you getting a permit (with
PE drawings)?
>
> Here is what I have for my 140 foot tower
> 2000 ft guy cable 1/4 inch
Is the cable EHS? Rohn specs for 25G DO NOT call for 1/4 inch EHS guys
but do spec 3/16 inch EHS. Since the leg strength is the limiting factor on
25G loading, I would suggest not using the 1/4 inch cable.
> 64 cable clamps
> 3 GA25GD Guy bracket
> 1 TA25 Torque arm.
>
Your message stopped here for some reason.
Cheers, Steve K7LXC
--