[TenTec] RE: Experience with UPS and ham rigs

To: <tentec@contesting.com>
Subject: [TenTec] RE: Experience with UPS and ham rigs
From: AC5E@aol.com (AC5E@aol.com)
Date: Wed May 21 15:25:32 2003
Since it's been suggested - I have tried several "small"  375-425 VA UPS on 
an Omni VI -  usually to allow us to operate FD while the generators were 
shut down. The setups were Astron 35's powering the rig and a keyer, and the 
usual result was a blown UPS fuse within a few seconds of changeover - and in 
one case a well fried UPS.  

I think the problem is with the really poor output of the cheaper UPS, since 
a couple of "pure sine wave" 1500 VA UPS did quite well. But those big boy's 
are a long way from cheap. 

And, one more thing. You definitely want to proved forced air ventilation for 
any unsealed lead acid battery you might be using. A little accumulated 
hydrogen makes a big bang. 

73  Pete Allen  AC5E

 