I am using a big 30 amp 240V variac here and it would trip my 30 amp 240V
breaker when I powered up the variac on it's own with no load. I had to
install a surge limiter on the variac to prevent this from happening FYI
73 Mark N1UK
----- Original Message -----
From: "glenn riccio" <gfriccio@hughes.net>
To: <amps@contesting.com>
Sent: Saturday, 30 August, 2014 6:51 PM
Subject: [Amps] solid state relays
Hello all , I'm in the process of collecting components for another GG amp
I
am building.
I have some questions on the hv power supply. I'm building a very
conventional supply. Most schemes use a big ole contactor and power
resistor
for the soft start circuit on the primary side ( of course) . Has any one
tried using a solid state soft start relay instead ? Crydom has several
that
I'm considering. They all need DC for the input switching , but could just
build a little 12v dc supply for it. I'm using a big Variac in the primary
side and don't want a conventional contactor because it might kick out at
lower voltage settings. Any advice would be appreciated. Thanks , Glenn
K7GFR