## Good point. My yaesu FT-1000D sucks 1050 VA from the wall plug, yet only puts 200w into a dummy load. It only runs 50% PA eff too. So 400 w dc input to get 200w output.
It doesn’t use a switcher either....just a huge torroid.

##  But sucking 1050 VA is plane nuts.  That implies a .2 PF.
Heck, any tube type kw linear amp is way better than that, typ with a .85 to .90 PF.

## Has anybody actually measured the PF on a transformerless supply, with a big C filter ??? I cant see it being any worse than your typ kw tube amp....with the typ xfmr + FWB / Doubler + high C filter. Another option would be to use a transformerless supply + a choke input or
resonant choke input.

## Your typ commercial 1.5 kw CCS SS amp is huge $$ these days. The switching supply is the cheapest part. $475.00 for a 3.3 kw CCS switcher...... and unity/perfect PF to boot ! So the real savings in any transformerless scheme is minimal at best......and NO PF correction either. You could probably
series 2  or more  switchers in series for more VDD.

Jim   VE7RF





-----Original Message----- From: peter chadwick
Sent: Sunday, September 22, 2013 1:08 PM
To: Jim Thomson ; amps@contesting.com
Subject: RE: [Amps] Direct rectification of AC mains to drive the amp,

Jim,

What about power factor correction circuitry?

73

Peter G3RZP


========================================
Message Received: Sep 22 2013, 06:27 PM
From: "Jim Thomson" <jim.thom@telus.net>
To: amps@contesting.com
Cc:
Subject: [Amps]  Direct rectification of AC mains to drive the amp,

Date: Sat, 21 Sep 2013 09:50:52 -0700
From: Don Jones <ko7i@comcast.net>
To: amps@contesting.com
Subject: Re: [Amps] Direct rectification of AC mains to drive the amp,
VDD Supply

This is tricky. If the outlet you are using as the source is not daisy
chained to a bunch of other outlets and goes directly to the panel, and
you use a true 3 wire connection L1, L2 (or N) and Gnd, you can "get
away" with it provided you use an appropriately selected EMC filter too.
It is safe and efficient? no, heed the advice that you have been given
by others.
Vy 73, Don KO7i.

## Why wouldn’t it be efficient ? With direct rectification you just eliminated
the xfmr !   Now you have NO limit to the amount of power you can generate.
No V drop across any xfmr either, no sag...no xfmr. Both static and dynamic regulation would be better, a lot better. No magnetizing current on the primary of the xfmr as there is no xfmr. No heat generated from the xfmr...as there is NO xfmr. You also just freed up a ton of
space.  You also eliminated  a ton of weight.

## For high power use, Id say it’s the ideal ticket. All you need is big ga CU wire back to the main 200A panel. I would not write off a transformerless supply just yet. I think we are just getting
started.   240 x 1.414 =   340 vdc.......and  @  10-100A  CCS easily.

Jim  VE7RF