- 1. [AMPS] Re:230 /115 volts QUIZ. (score: 1)
- Author: wb4mnf@atl.org (Bob Duckworth)
- Date: Mon, 9 Apr 2001 09:24:32 -0400
- Who knows about a "high leg" on a three phase system? Have this at my shop. Three phase (4 wire plus ground). One of three phase is marked "high leg". Between the other two phases and neutral, I see
- /archives//html/Amps/2001-04/msg00191.html (7,610 bytes)
- 2. [AMPS] Re:230 /115 volts QUIZ. (score: 1)
- Author: W8JI@contesting.com (Tom Rauch)
- Date: Mon, 9 Apr 2001 10:31:43 -0400
- Wild-leg three-phase is common, and the configuration can be a Wye or Delta. Where the configuration is a delta, one 240 v transformer secondary is connected the normal way. Each of the two hot phas
- /archives//html/Amps/2001-04/msg00197.html (8,914 bytes)
- 3. [AMPS] Re:230 /115 volts QUIZ. (score: 1)
- Author: John Ferebee" <john@480volts.ac (John Ferebee)
- Date: Mon, 9 Apr 2001 12:48:42 -0400
- Bob: 3 phase Delta four(4) wire: 0A to neu - 120V 0B to neu - 208V 'wild leg' 0C to neu - 120V 0A to 0B - 240V 0B to 0C - 240V 0A to 0C - 240V Note: The '0' is phase but I cannot make a '0' with a sl
- /archives//html/Amps/2001-04/msg00201.html (8,830 bytes)
- 4. [AMPS] Re:230 /115 volts QUIZ. (score: 1)
- Author: 2@vc.net (measures)
- Date: Mon, 9 Apr 2001 13:55:29 -0700
- On the Macintosh OS, shift-option-o makes a Ø. - Rich..., 805.386.3734, www.vcnet.com/measures. end -- FAQ on WWW: http://www.contesting.com/FAQ/amps Submissions: amps@contesting.com Administ
- /archives//html/Amps/2001-04/msg00210.html (7,787 bytes)
- 5. [AMPS] Re:230 /115 volts QUIZ. (score: 1)
- Author: huntleyr@gte.net (Roger Huntley)
- Date: Tue, 10 Apr 2001 03:26:25 +0100
- Bob, What you have is a 240/120 Volt, 3-Phase, 4-Wire grounded delta service. You did not state what the phase-to-phase voltage is but it probably is 240 Volts. Not knowing where you are located you
- /archives//html/Amps/2001-04/msg00221.html (10,699 bytes)
- 6. [AMPS] Re:230 /115 volts QUIZ. (score: 1)
- Author: wb4mnf@atl.org (Bob Duckworth)
- Date: Tue, 10 Apr 2001 16:59:38 -0400
- Thanks for all info... It looks like I have the 4 wire delta with the center tapped winding for 120. I'll try to verify by looking at the transformer... -bob -- FAQ on WWW: http://www.contesting.com/
- /archives//html/Amps/2001-04/msg00239.html (7,419 bytes)
This search system is powered by
Namazu