Patrick,
I agree, "different strokes" but to understand the principles, the 
Carrier Psychometric Chart was pretty helpful to me as it sorts out Rh 
from dew point and shows "lbs of moisture per pound of dry air". It was 
developed for HVAC uses. 
http://www.handsdownsoftware.com/carrier-chart.pdf
The variables for conduit are its (ground) temperature and air flow 
water content.  I think that occupied buildings almost always have lower 
Rh than outside - heated in winter, AC in summer.  That doesn't mean the 
inside air dew point is lower than that inside the conduit, which 
determines if there will be condensation.  If temps inside the conduit 
are higher than dew point, no condensation and evaporation of water that 
is present.  When reversed there is condensation, eg frozen ground and 
warm outside temps.  Venting to outside is another set of differential 
temperatures and water content circumstances. 
So IMO, with varying seasons, lagging ground temps and variable inside 
(or vented) temps and moisture levels, it seems almost certain to get 
condensation at times in the conduit (extreme desert climates 
excepted).  Sealing may help if done at the right time, but hermetic 
seals that prevent in/out air flow are really hard. Broadcast stations 
sometimes purge air dielectric coax with calibrated dry gases, bottled 
N2 or dry air from a refrigerated dryer or desiccant system or both.  
Then dew points are known to be in well into negative F temps  (eg 
-40).  Possible, but a bit over the top for hams. 
So my approach, since in conduit condensation is highly likely,  is to 
always use direct burial cables in conduit with no connectors or breaks 
in cables.  The polyethylene (PE) covered RG's or Heliax are my choice 
as are PE sheathed control cables and UF rated power cables (which go in 
the trench for AC, not inside the conduit for me).  And water tight 
conduits with glued joints.  Generally schedule 40 PVC but SDR35 is a 
good and cheaper choice for large diameters.  Drain pipe IMO doesn't 
make water tight seals with the gaskets.  Why let in ground water and 
dirt?  I've seen the water flowing out of conduit (and out of coax!) as 
you had when there is a hole in the conduit. 
This is an interesting topic, maybe a few hundred threads about it on 
TT, but probably 97% of water in coax is due to poor connector sealing. 
Grant KZ1W
On 1/31/2018 5:54 AM, Patrick Greenlee wrote:
 Different strokes... Some, like Chick, vent underground conduit to the 
surface air, others put drain holes in the underside, some try to seal 
it up (with or without desiccant), others purge with "dry" air 
intermittently or warm dry air continuously, others may get good 
results doing nothing extra, and so on and so forth  A N D  most say 
"it works for me." There probably is no single best answer, certainly 
with the wide variety of climates.  In some places if you tried drain 
holes the ground water would flood your conduit.  Some places venting 
to surface air will allow condensation in the vent pipes as temps and 
RH go through the diurnal cycle adding water to your buried conduit 
over time.
If the conduit is sealed well one of the few ways for moisture to gain 
entry is via poorly sealed coax.  Moisture can egress via the shield 
of improperly sealed coax. I did nothing "heroic", just installed my 
various PVC conduits with plenty glue, a twist, and hold fully engaged 
for 30 sec to get a proper glued joint.  When going back to a 
previously wired conduit to add more wires I never detected any 
moisture. I guess I'm lucky to be fortunate enough to have benighn 
conditions that don't require special amelioration. 
One glaring oops in my conduit experiences is the last 4 inch S&D run 
which is a minor embarrassment in that during backfilling I got lazy 
and too hurried in backfilling and ended up with rocks and large hard 
clods in the backfill against the conduit which when driven over 
damaged the conduit. How do I know the conduit was damaged? Ground 
water entered the conduit which was on a slope which made a 
considerable head of pressure and over flowed the terminal end of the 
conduit which was 2 ft above my barn floor. Water poured out onto the 
slab at a rate of several gallons per minute.  I used a cordless 4 1/2 
inch angle grinder to cut a relief hole just above grade outside of 
the building so the water stays out side the building. 
Now what to do to salvage the situation, preferably without replacing 
the conduit.  Local big box stores sell rolls of 1" flexible 
irrigation pipe rated at 100PSI for $12.  I pulled my wires and cables 
into some of these, sealed the ends super water tight and then pulled 
those through the flooded conduit. 
My cables are still in the PVC conduit and so protected from the evil 
cable munching critters we have that delight in chewing on direct bury 
cables  A N D  they are protected from water up to 100 PSI (not likely 
to  be a problem.) The best part was not digging up and replacing the 
conduit.  A side benefit is that additional wires could be placed 
inside another run of 1 inch irrigation tubing and easily pulled along 
current cables as the irrigation tubing gives you a smooth 
non-snagging pulling experience. 
Hopefully none of you TowerTalkers will need to use my remedy but 
there it is, just in case. 
Patrick        NJ5G
On 1/30/2018 4:02 PM, Chick Allen via TowerTalk wrote:
 One thing to consider that will mitigate the "wet location" issue is 
to vent the conduit with some vents installed along the conduit.  
This is done using a simple pvc "tee".  If you're using 2" pvc, just 
connect the lengths at several different points with a 2"x2"x2" tee, 
reduce the vertical tee to something smaller, like 1" or 3/4" and 
bring that about one foot above the ground.  There you can add a 
sweep el that will prevent moisture from entering the conduit while 
allowing condensation to evaporate.  Plan your above ground vents 
around a fence post or some other above ground object so it won't get 
broken as easily.  Otherwise, a short piece of treated 4"x4" will 
provide a stable support.  Works for me.
73 de Chick / NW3Y
-----Original Message-----
From: Shane Youhouse <kd6vxi@gmail.com>
To: towertalk <towertalk@contesting.com>
Sent: Tue, Jan 30, 2018 2:34 pm
Subject: [TowerTalk] Pulling coax through PVC pipe
I wouldn't be so quick to run ANY romex through PVC when it's 
buried.  It's 
against code.
Article 300 of the NEC states any buried pipe is considered a wet 
location. 
*300.5 Underground Installations.*
*(B) Wet Locations.* The interior of enclosures or raceways installed
underground shall be considered to be a wet location. Insulated 
conductors 
and cables installed in these enclosures or raceways in underground
installations shall be listed for use in wet locations and shall comply
with 310.10(C). Any connections or splices in an underground 
installation 
shall be approved for wet locations.
Then, article 334 implicitly states you may NOT use romex (NM) in damp
locations.
*334.12 Uses Not Permitted.*
*(B) Types NM and NMS*. Types NM and NMS cables shall not be used 
under the 
following conditions or in the following locations:
(4) In wet or damp locations
As such, you are MUCH better off running single runs of wire in 
addition to 
a heavy ground to keep SPG intact
There are a LOT more rules regarding NM style wiring, but this is the 
gist. 
Also, it's not always wrong to mix 120 volt and low voltage.  As long as
you use THHN or other 600 volt insulation and all wiring is class 1, 
you're 
OK.
--Shane
KD6VXI
_______________________________________________
_______________________________________________
TowerTalk mailing list
TowerTalk@contesting.com
http://lists.contesting.com/mailman/listinfo/towertalk
_______________________________________________
_______________________________________________
TowerTalk mailing list
TowerTalk@contesting.com
http://lists.contesting.com/mailman/listinfo/towertalk
 
_______________________________________________
_______________________________________________
TowerTalk mailing list
TowerTalk@contesting.com
http://lists.contesting.com/mailman/listinfo/towertalk
 
_______________________________________________
_______________________________________________
TowerTalk mailing list
TowerTalk@contesting.com
http://lists.contesting.com/mailman/listinfo/towertalk
 |