On Sat,1/9/2016 8:10 PM, Larry wrote:
The Polyphaser book on grounding recommended that ground rods be spaced about twice the length of the rods (e.g., 16 feet spacing for 8 foot rods). Presumably that will help with the charge saturation during an event.

The reason for rod spacing is to minimize inductive coupling between them, which reduces their effectiveness.

73, Jim K9YC