[TowerTalk] Mixing Galvanized & Copper Ground Rods

To: towertalk@contesting.com
Subject: [TowerTalk] Mixing Galvanized & Copper Ground Rods
From: doc <kd4e@verizon.net>
Reply-to: kd4e@verizon.net
Date: Mon, 27 Jun 2005 09:40:30 -0400
List-post: <mailto:towertalk@contesting.com>
I think I already know the answer to this but would like the benefit
of the gathered wisdom of list members if I may?

The power company here in West Central Florida installed two galvanized
ground rods at the breaker box.

Because the soil is sugar sand, and because I need to mount a 
copper-nickel plate for the lightning protection devices, I need to 
install another four rods and am wondering if it matters if I install
copper or galvanize pipe or rod.

The concern is about mixing metals in close proximity, 8-10" at the
closest point.

-- 
Thanks! & 73, doc kd4e

           |_|___|_|
           | | & | |
              {|
      /\      {|
     /  \     {|
    /    \    {|
   /   @  \   {|
   |   |~_|~~~~|
   |   -| |    |
============\ #    West Central Florida
     KD4E     ==============================
http://bibleseven.com
Ham PC = 100% Linux Novell-Suse 9.2
Halli, Heathkit, Homebrew, MFJ, TenTec, Yaesu
Radio Life: http://www.gospelcom.net/twr/
Linux-Incompatible hardware is defective!
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
_______________________________________________

See: http://www.mscomputer.com  for "Self Supporting Towers", "Wireless Weather 
Stations", and lot's more.  Call Toll Free, 1-800-333-9041 with any questions 
and ask for Sherman, W2FLA.

_______________________________________________
TowerTalk mailing list
TowerTalk@contesting.com
http://lists.contesting.com/mailman/listinfo/towertalk

<Prev in Thread] Current Thread [Next in Thread>
  • [TowerTalk] Mixing Galvanized & Copper Ground Rods, doc <=