On Oct 13, 2005, at 2:55 PM, Gudguyham@aol.com wrote:



In a message dated 10/13/2005 3:16:50 P.M. Eastern Standard Time, r@somis.org writes:
.  I read that you should never
> connect neutral and ground together at any place other than the entry
> panel as a difference in voltage potential could exist.


This is CORRECT!

However, with a 30-ft run of #10 Cu, R is c. 0.031Ω, so at enough current to trip the 30A circuit breakers, there could be a few tenths of a volt drop in the neutral wire for a few seconds until the breakers trip. Thank you, Mr. Ohm.


Richard L. Measures, AG6K, 805.386.3734. www.somis.org