>OK, I'm practically finished with the power supply section of my 1500 watt
>amp.
>The plate transformer is rated at 2400 vac at 1a CCS, and there is an
additional
>140 watts of filament power, 120 watts worth of blower, and maybe another 50
>watts of miscellaneous draw, totalling 2710 watts.
>
>There's a soft-start circuit in the plate and filament circuits that puts
>a 25 ohm resistor in the primary circuit at startup.
>
sounds good
>2710w / 220v = 12.3a + 20% = 14.8 amps. Should I use 15 amp fuses or 20 amp
>fuses? I presume that I should choose slow-blow fuses because of the peak
>repetitive current.
>
With a C-filter, slow blow is the only game in town. However, if there
is a slow blow circuit-breaker in the branch, you don't need no stinkin'
fuses.
- cheers, Vic