Re: [Amps] questions on my transformer test

To: <amps@contesting.com>, "Will Matney" <craxd@engineer.com>
Subject: Re: [Amps] questions on my transformer test
From: "kenw2dtc" <kenw2dtc@comcast.net>
Date: Tue, 14 Jun 2005 01:09:49 -0400
List-post: <mailto:amps@contesting.com>
Will,
I agree with you on measuring the wire size; however, upon investigation the
secondary terminals are fed with , thick flat copper bus which has much more
area then the actual secondary wires, so I'm not going to tear open the
beast to find the wires.   A couple of other gentlemen suggested that maybe
the transformer has a 2 amp rating, so for the heck of it I ran the test for
6 hours at 2.0 amps and the internal temperature was 144.   The first few 
hours
did yield about 110 degrees as you suggested.

73,
Ken W2DTC

----- Original Message ----- 
From: "Will Matney" <craxd@engineer.com>
To: <amps@contesting.com>
Sent: Tuesday, June 14, 2005 12:03 AM
Subject: Re: [Amps] questions on my tranformer test


> Ken, the watt rating can be determined by the core size and then the 
> current found from that. But, that dont hold true if they didn't wind the 
> coil with the right size wire for its duty cycle. The only way you can 
> tell for sure is find the wire size used in the coil. If you knew what the 
> wire insulation was, so to know its temperature rating, you could snake a 
> thermostat wire down in the center of the winding and run it under load to 
> see what the coils innards are heating to. Or do the hope-so test and see 
> how hot the core and coil gets by touch which isn't accurate. If its right 
> for the load, the core and coil should just be warm to the touch, and not 
> close to hot enough as you couldn't keep your hand on it. 180 degrees is 
> way too hot for any to run. Something in the order of 100 degrees to maybe 
> 110 is about maximum for one in open air.
>
> Best,
>
> Will
>
> ----- Original Message -----
> From: kenw2dtc <kenw2dtc@comcast.net>
> To: amps@contesting.com
> Subject: [Amps] questions on my tranformer test
> Date: Sun, 12 Jun 2005 14:39:52 -0400
>
>>
>> Hi,
>> I'm trying to figure out the current rating of a plate transformer.  This 
>> is
>> my test setup:
>>
>> http://w2dtc.com/2005-0610-transformer-test-page.htm
>>
>> Questions:
>> 1.  Is this a valid way to find the secondary current capability?
>> 2.  Is the internal temperature of 180 degrees F too high for a 
>> transformer
>> under load for 5 hours?
>> 3.  Is there a problem running this center tapped beast in a full wave
>> capacitive input configuration?
>>
>> Thanks and 73,
>> Ken W2DTC
>>
>>
>>
>>
>> _______________________________________________
>> Amps mailing list
>> Amps@contesting.com
>> http://lists.contesting.com/mailman/listinfo/amps
>
>
> -- 
> ___________________________________________________________
> Sign-up for Ads Free at Mail.com
> http://promo.mail.com/adsfreejump.htm
>
> _______________________________________________
> Amps mailing list
> Amps@contesting.com
> http://lists.contesting.com/mailman/listinfo/amps 

_______________________________________________
Amps mailing list
Amps@contesting.com
http://lists.contesting.com/mailman/listinfo/amps

<Prev in Thread] Current Thread [Next in Thread>